S11 Oil-Immersed Transformer for 10 kV & 35 kV Networks
Oil-immersed transformer with off-circuit tap changing.

Key facts
Oil-immersed transformer with off-circuit tap changing.
- 10 kV & 35 kV published voltage classes
- Off-circuit tap changing
- Oil-insulated construction
- 30–31,500 kVA across the published tables
- Voltage class
- 10 kV & 35 kV
- Frequency
- 50 Hz
- Installation
- Indoor / outdoor
Published normal service conditions: −25 °C to +40 °C; altitude below 1,000 m. Specify site conditions in your enquiry.
Request datasheetTechnical parametersLead time confirmed per order.
Technical parameters
Scroll each table horizontally on smaller screens. Values below are from the factory’s product document; confirm the final configuration with the technical team.
| Rated capacity (kVA) | No-load loss (kW) | Load loss at 75 °C (kW) | No-load current (%) | Impedance (%) |
|---|---|---|---|---|
| 30 | 0.10 | 0.63/0.60 | 1.50 | 4.0 |
| 50 | 0.13 | 0.91/0.87 | 1.30 | 4.0 |
| 80 | 0.18 | 1.31/1.25 | 1.20 | 4.0 |
| 100 | 0.20 | 1.58/1.50 | 1.10 | 4.0 |
| 125 | 0.24 | 1.89/1.80 | 1.10 | 4.0 |
| 160 | 0.28 | 2.31/2.20 | 1.00 | 4.0 |
| 200 | 0.34 | 2.73/2.60 | 1.00 | 4.0 |
| 250 | 0.40 | 3.20/3.05 | 0.90 | 4.0 |
| 315 | 0.48 | 3.83/3.65 | 0.90 | 4.0 |
| 400 | 0.57 | 4.52/4.30 | 0.80 | 4.0 |
| 500 | 0.68 | 5.41/5.15 | 0.80 | 4.0 |
| 630 | 0.81 | 6.20 | 0.60 | 4.5 |
| 800 | 0.98 | 7.50 | 0.60 | 4.5 |
| 1000 | 1.15 | 10.3 | 0.60 | 4.5 |
| 1250 | 1.36 | 12.0 | 0.50 | 4.5 |
| 1600 | 1.64 | 14.5 | 0.50 | 4.5 |
| 2000 | 1.94 | 18.3 | 0.40 | 5.0 |
| 2500 | 2.29 | 21.2 | 0.40 | 5.0 |
| Rated capacity (kVA) | High voltage (kV) | HV tapping range (source notation) | Low voltage (kV) | Connection group |
|---|---|---|---|---|
| 30 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 50 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 80 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 100 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 125 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 160 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 200 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 250 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 315 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 400 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 500 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 630 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 800 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 1000 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 1250 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 1600 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 2000 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
| 2500 | 6 / 6.3 / 10 / 10.5 / 11 | ±5%or ±2×2.5% | 0.4 | Yyn0 / Dyn11 / Yzn11 |
Slash-separated entries are alternatives. Tapping notation is retained from the source; where a percent sign or value is absent, request confirmation before selection.
| Rated capacity (kVA) | No-load loss (kW) | Load loss at 75 °C (kW) | No-load current (%) | Impedance (%) |
|---|---|---|---|---|
| 50 | 0.16 | 1.20/1.14 | 1.3 | 6.5 |
| 100 | 0.23 | 2.01/1.91 | 1.1 | 6.5 |
| 125 | 0.27 | 2.37/2.26 | 1.1 | 6.5 |
| 160 | 0.28 | 2.82/2.68 | 1.0 | 6.5 |
| 200 | 0.34 | 3.32/3.16 | 1.0 | 6.5 |
| 250 | 0.40 | 3.95/3.76 | 0.95 | 6.5 |
| 315 | 0.48 | 4.75/4.53 | 0.95 | 6.5 |
| 400 | 0.58 | 5.74/5.47 | 0.85 | 6.5 |
| 500 | 0.68 | 6.91/6.58 | 0.85 | 6.5 |
| 630 | 0.83 | 7.86 | 0.65 | 6.5 |
| 800 | 0.98 | 9.40 | 0.65 | 6.5 |
| 1000 | 1.15 | 11.5 | 0.65 | 6.5 |
| 1250 | 1.40 | 13.9 | 0.60 | 6.5 |
| 1600 | 1.69 | 16.6 | 0.60 | 6.5 |
| 2000 | 1.99 | 19.7 | 0.55 | 6.5 |
| 2500 | 2.36 | 23.2 | 0.55 | 6.5 |
| Rated capacity (kVA) | High voltage (kV) | HV tapping range (source notation) | Low voltage (kV) | Connection group |
|---|---|---|---|---|
| 50 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 100 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 125 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 160 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 200 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 250 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 315 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 400 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 500 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 630 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 800 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 1000 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 1250 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 1600 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 2000 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
| 2500 | 35 / 38.5 | ±5 / ±2×2.5 | 0.4 | Dyn11 / Yyn0 |
Slash-separated entries are alternatives. Tapping notation is retained from the source; where a percent sign or value is absent, request confirmation before selection.
| Rated capacity (kVA) | No-load loss (kW) | Load loss at 75 °C (kW) | No-load current (%) | Impedance (%) |
|---|---|---|---|---|
| 630 | 0.83 | 7.86 | 0.65 | 6.5 |
| 800 | 0.98 | 9.4 | 0.65 | 6.5 |
| 1000 | 1.15 | 11.5 | 0.65 | 6.5 |
| 1250 | 1.40 | 13.9 | 0.55 | 6.5 |
| 1600 | 1.69 | 16.6 | 0.45 | 6.5 |
| 2000 | 2.17 | 18.3 | 0.45 | 6.5 |
| 2500 | 2.56 | 19.6 | 0.45 | 6.5 |
| 3150 | 3.04 | 23.0 | 0.45 | 7.0 |
| 4000 | 3.61 | 27.3 | 0.45 | 7.0 |
| 5000 | 4.32 | 31.3 | 0.45 | 7.0 |
| 6300 | 5.24 | 35.0 | 0.45 | 8.0 |
| 8000 | 7.20 | 38.4 | 0.35 | 8.0 |
| 10000 | 8.70 | 45.3 | 0.35 | 8.0 |
| 12500 | 10.0 | 53.8 | 0.30 | 8.0 |
| 16000 | 12.1 | 65.8 | 0.30 | 8.0 |
| 20000 | 14.4 | 79.5 | 0.30 | 8.0 |
| 25000 | 17.0 | 94.0 | 0.25 | 10.0 |
| 31500 | 20.2 | 112 | 0.25 | 10.0 |
| Rated capacity (kVA) | High voltage (kV) | HV tapping range (source notation) | Low voltage (kV) | Connection group |
|---|---|---|---|---|
| 630 | 35 | ±5 / ±2×2.5 | 3.15 / 6.3 / 10.5 | Yd11 |
| 800 | 35 | ±5 / ±2×2.5 | 3.15 / 6.3 / 10.5 | Yd11 |
| 1000 | 35 | ±5 / ±2×2.5 | 3.15 / 6.3 / 10.5 | Yd11 |
| 1250 | 35 | ±5 / ±2×2.5 | 3.15 / 6.3 / 10.5 | Yd11 |
| 1600 | 35 | ±5 / ±2×2.5 | 3.15 / 6.3 / 10.5 | Yd11 |
| 2000 | 35 | ±5 / ±2×2.5 | 3.15 / 6.3 / 10.5 | Yd11 |
| 2500 | 35 | ±5 / ±2×2.5 | 3.15 / 6.3 / 10.5 | Yd11 |
| 3150 | 35 / 38.5 | ±5 / ±2×2.5 | 3.15 / 6.3 / 10.5 | Yd11 |
| 4000 | 35 / 38.5 | ±5 / ±2×2.5 | 3.15 / 6.3 / 10.5 | Yd11 |
| 5000 | 35 / 38.5 | ±5 / ±2×2.5 | 3.15 / 6.3 / 10.5 | Yd11 |
| 6300 | 35 / 38.5 | ±5 / ±2×2.5 | 3.15 / 6.3 / 10.5 | Yd11 |
| 8000 | 35 / 38.5 | ±2×2.5 | 3.15 / 3.3 / 6.3 / 6.6 / 10.5 | YNd11 |
| 10000 | 35 / 38.5 | ±2×2.5 | 3.15 / 3.3 / 6.3 / 6.6 / 10.5 | YNd11 |
| 12500 | 35 / 38.5 | ±2×2.5 | 3.15 / 3.3 / 6.3 / 6.6 / 10.5 | YNd11 |
| 16000 | 35 / 38.5 | ±2×2.5 | 3.15 / 3.3 / 6.3 / 6.6 / 10.5 | YNd11 |
| 20000 | 35 / 38.5 | ±2×2.5 | 3.15 / 3.3 / 6.3 / 6.6 / 10.5 | YNd11 |
| 25000 | 35 / 38.5 | ±2×2.5 | 3.15 / 3.3 / 6.3 / 6.6 / 10.5 | YNd11 |
| 31500 | 35 / 38.5 | ±2×2.5 | 3.15 / 3.3 / 6.3 / 6.6 / 10.5 | YNd11 |
Slash-separated entries are alternatives. Tapping notation is retained from the source; where a percent sign or value is absent, request confirmation before selection.