Key facts

Oil-immersed transformer with off-circuit tap changing.

  • 10 kV & 35 kV published voltage classes
  • Off-circuit tap changing
  • Oil-insulated construction
  • 30–31,500 kVA across the published tables
Voltage class
10 kV & 35 kV
Frequency
50 Hz
Installation
Indoor / outdoor

Published normal service conditions: −25 °C to +40 °C; altitude below 1,000 m. Specify site conditions in your enquiry.

Request datasheetTechnical parameters

Lead time confirmed per order.

Technical parameters

Scroll each table horizontally on smaller screens. Values below are from the factory’s product document; confirm the final configuration with the technical team.

S11-30-2500/10/0.4
Rated capacity (kVA)No-load loss (kW)Load loss at 75 °C (kW)No-load current (%)Impedance (%)
300.100.63/0.601.504.0
500.130.91/0.871.304.0
800.181.31/1.251.204.0
1000.201.58/1.501.104.0
1250.241.89/1.801.104.0
1600.282.31/2.201.004.0
2000.342.73/2.601.004.0
2500.403.20/3.050.904.0
3150.483.83/3.650.904.0
4000.574.52/4.300.804.0
5000.685.41/5.150.804.0
6300.816.200.604.5
8000.987.500.604.5
10001.1510.30.604.5
12501.3612.00.504.5
16001.6414.50.504.5
20001.9418.30.405.0
25002.2921.20.405.0
S11-30-2500/10/0.4 voltage and connection options
Rated capacity (kVA)High voltage (kV)HV tapping range (source notation)Low voltage (kV)Connection group
306 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
506 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
806 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
1006 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
1256 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
1606 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
2006 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
2506 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
3156 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
4006 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
5006 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
6306 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
8006 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
10006 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
12506 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
16006 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
20006 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11
25006 / 6.3 / 10 / 10.5 / 11±5%or ±2×2.5%0.4Yyn0 / Dyn11 / Yzn11

Slash-separated entries are alternatives. Tapping notation is retained from the source; where a percent sign or value is absent, request confirmation before selection.

S11-50-2500/35/0.4
Rated capacity (kVA)No-load loss (kW)Load loss at 75 °C (kW)No-load current (%)Impedance (%)
500.161.20/1.141.36.5
1000.232.01/1.911.16.5
1250.272.37/2.261.16.5
1600.282.82/2.681.06.5
2000.343.32/3.161.06.5
2500.403.95/3.760.956.5
3150.484.75/4.530.956.5
4000.585.74/5.470.856.5
5000.686.91/6.580.856.5
6300.837.860.656.5
8000.989.400.656.5
10001.1511.50.656.5
12501.4013.90.606.5
16001.6916.60.606.5
20001.9919.70.556.5
25002.3623.20.556.5
S11-50-2500/35/0.4 voltage and connection options
Rated capacity (kVA)High voltage (kV)HV tapping range (source notation)Low voltage (kV)Connection group
5035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
10035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
12535 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
16035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
20035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
25035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
31535 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
40035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
50035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
63035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
80035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
100035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
125035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
160035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
200035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0
250035 / 38.5±5 / ±2×2.50.4Dyn11 / Yyn0

Slash-separated entries are alternatives. Tapping notation is retained from the source; where a percent sign or value is absent, request confirmation before selection.

S11-630-31500/35/10.5
Rated capacity (kVA)No-load loss (kW)Load loss at 75 °C (kW)No-load current (%)Impedance (%)
6300.837.860.656.5
8000.989.40.656.5
10001.1511.50.656.5
12501.4013.90.556.5
16001.6916.60.456.5
20002.1718.30.456.5
25002.5619.60.456.5
31503.0423.00.457.0
40003.6127.30.457.0
50004.3231.30.457.0
63005.2435.00.458.0
80007.2038.40.358.0
100008.7045.30.358.0
1250010.053.80.308.0
1600012.165.80.308.0
2000014.479.50.308.0
2500017.094.00.2510.0
3150020.21120.2510.0
S11-630-31500/35/10.5 voltage and connection options
Rated capacity (kVA)High voltage (kV)HV tapping range (source notation)Low voltage (kV)Connection group
63035±5 / ±2×2.53.15 / 6.3 / 10.5Yd11
80035±5 / ±2×2.53.15 / 6.3 / 10.5Yd11
100035±5 / ±2×2.53.15 / 6.3 / 10.5Yd11
125035±5 / ±2×2.53.15 / 6.3 / 10.5Yd11
160035±5 / ±2×2.53.15 / 6.3 / 10.5Yd11
200035±5 / ±2×2.53.15 / 6.3 / 10.5Yd11
250035±5 / ±2×2.53.15 / 6.3 / 10.5Yd11
315035 / 38.5±5 / ±2×2.53.15 / 6.3 / 10.5Yd11
400035 / 38.5±5 / ±2×2.53.15 / 6.3 / 10.5Yd11
500035 / 38.5±5 / ±2×2.53.15 / 6.3 / 10.5Yd11
630035 / 38.5±5 / ±2×2.53.15 / 6.3 / 10.5Yd11
800035 / 38.5±2×2.53.15 / 3.3 / 6.3 / 6.6 / 10.5YNd11
1000035 / 38.5±2×2.53.15 / 3.3 / 6.3 / 6.6 / 10.5YNd11
1250035 / 38.5±2×2.53.15 / 3.3 / 6.3 / 6.6 / 10.5YNd11
1600035 / 38.5±2×2.53.15 / 3.3 / 6.3 / 6.6 / 10.5YNd11
2000035 / 38.5±2×2.53.15 / 3.3 / 6.3 / 6.6 / 10.5YNd11
2500035 / 38.5±2×2.53.15 / 3.3 / 6.3 / 6.6 / 10.5YNd11
3150035 / 38.5±2×2.53.15 / 3.3 / 6.3 / 6.6 / 10.5YNd11

Slash-separated entries are alternatives. Tapping notation is retained from the source; where a percent sign or value is absent, request confirmation before selection.