Transformer manufacturing in Tai’an, Shandong, China[email protected]
Daifeng registered trademarkTBDL TransformerShandong Tebian Electric Power Equipment Co., Ltd.Get a quote

SZ13 Oil-Immersed Transformer for 10 kV & 35 kV Networks

Oil-immersed transformer with on-load tap changing.

Factory photograph of an oil-immersed transformer
Product family photograph. Supplied configuration may differ.

Key facts

Oil-immersed transformer with on-load tap changing.

  • 10 kV & 35 kV published voltage classes
  • On-load tap changing
  • Oil-insulated construction
  • 200–31,500 kVA across the published tables
Voltage class
10 kV & 35 kV
Frequency
50 Hz
Installation
Indoor / outdoor

Published normal service conditions: −25 °C to +40 °C; altitude below 1,000 m. Specify site conditions in your enquiry.

Request datasheetTechnical parameters

Lead time confirmed per order.

Technical parameters

Scroll each table horizontally on smaller screens. Values below are from the factory’s product document; confirm the final configuration with the technical team.

SZ13-200-2500/10/0.4
Rated capacity (kVA)No-load loss (kW)Load loss at 75 °C (kW)No-load current (%)Impedance (%)
2000.3052.900.804.0
2500.3503.420.724.0
3150.4254.100.724.0
4000.5104.950.644.0
5000.6105.890.644.0
6300.7707.260.484.5
8000.8958.890.484.5
10001.0910.40.484.5
12501.2512.30.404.5
16001.5414.70.404.5
20001.8218.60.325.0
25002.1421.60.325.0
SZ13-200-2500/10/0.4 voltage and connection options
Rated capacity (kVA)High voltage (kV)HV tapping range (source notation)Low voltage (kV)Connection group
2006 6.3 / 10 10.5 11±4X2.5%0.4Yyn0 Dyn11
2506 6.3 / 10 10.5 11±4X2.5%0.4Yyn0 Dyn11
3156 6.3 / 10 10.5 11±4X2.5%0.4Yyn0 Dyn11
4006 6.3 / 10 10.5 11±4X2.5%0.4Yyn0 Dyn11
5006 6.3 / 10 10.5 11±4X2.5%0.4Yyn0 Dyn11
6306 6.3 / 10 10.5 11±4X2.5%0.4Yyn0 Dyn11
8006 6.3 / 10 10.5 11±4X2.5%0.4Yyn0 Dyn11
10006 6.3 / 10 10.5 11±4X2.5%0.4Yyn0 Dyn11
12506 6.3 / 10 10.5 11±4X2.5%0.4Yyn0 Dyn11
16006 6.3 / 10 10.5 11±4X2.5%0.4Yyn0 Dyn11
20006 6.3 / 10 10.5 11±4X2.5%0.4Yyn0 Dyn11
25006 6.3 / 10 10.5 11±4X2.5%0.4Yyn0 Dyn11

Slash-separated entries are alternatives. Tapping notation is retained from the source; where a percent sign or value is absent, request confirmation before selection.

SZ13-2000-31500/35/10.5
Rated capacity (kVA)No-load loss (kW)Load loss at 75 °C (kW)No-load current (%)Impedance (%)
20001.8418.20.406.5
25002.1819.60.406.5
31502.6023.50.407.0
40003.1027.60.407.0
50003.7032.50.407.0
63004.5034.90.408.0
80006.3038.60.328.0
100007.4045.60.328.0
125008.7054.00.288.0
1600010.566.80.288.0
2000012.478.60.288.0
2500014.692.90.2410.0
3150017.4110.20.2410.0
SZ13-2000-31500/35/10.5 voltage and connection options
Rated capacity (kVA)High voltage (kV)HV tapping range (source notation)Low voltage (kV)Connection group
200035±3×2.56.3 / 10.5Yd11
250035±3×2.56.3 / 10.5Yd11
315035 / 38.5±3×2.56.3 / 10.5Yd11
400035 / 38.5±3×2.56.3 / 10.5Yd11
500035 / 38.5±3×2.56.3 / 10.5Yd11
630035 / 38.5±3×2.56.3 / 10.5Yd11
800035 / 38.5±3×2.56.3 / 6.6 / 10.5YNd11
1000035 / 38.5±3×2.56.3 / 6.6 / 10.5YNd11
1250035 / 38.5±3×2.56.3 / 6.6 / 10.5YNd11
1600035 / 38.5±3×2.56.3 / 6.6 / 10.5YNd11
2000035 / 38.5±3×2.56.3 / 6.6 / 10.5YNd11
2500035 / 38.5±3×2.56.3 / 6.6 / 10.5YNd11
3150035 / 38.5±3×2.56.3 / 6.6 / 10.5YNd11

Slash-separated entries are alternatives. Tapping notation is retained from the source; where a percent sign or value is absent, request confirmation before selection.

For oil-immersed ratings up to 500 kVA with paired load-loss figures, the first value applies to Dyn11 and the second to Yyn0. Voltage combinations, tapping range and connection group must be confirmed for the selected rating.

Start with your power requirements.

Share your voltage, capacity and installation conditions.

Request a quote
EmailRequest a quote