SZCB10 Dry-Type Transformer for 10 kV Networks

Resin-insulated dry-type transformer with on-load tap changing for indoor distribution.

Factory photograph of a dry-type transformer
Product family photograph. Supplied configuration may differ.

Key facts

Resin-insulated dry-type transformer with on-load tap changing for indoor distribution.

  • 10 kV published voltage classes
  • On-load tap changing
  • Epoxy resin insulation
  • 315–2,500 kVA across the published tables
Voltage class
10 kV
Frequency
50 Hz
Installation
Indoor

Published normal service conditions: −25 °C to +40 °C; altitude below 1,000 m. Specify site conditions in your enquiry.

Request datasheetTechnical parameters

Lead time confirmed per order.

Technical parameters

Scroll each table horizontally on smaller screens. Values below are from the factory’s product document; confirm the final configuration with the technical team.

SZCB10-315-2500/10/0.4
Rated capacity (kVA)No-load loss (kW)Load loss at 120 °C (kW)No-load current (%)Impedance (%)
3150.993.611.104.0
4001.124.271.104.0
5001.295.201.104.0
6301.446.361.006.0
8001.717.501.006.0
10001.988.780.856.0
12502.3410.40.856.0
16002.7212.40.856.0
20003.4215.20.706.0
25003.9518.10.706.0
SZCB10-315-2500/10/0.4 voltage and connection options
Rated capacity (kVA)High voltage (kV)HV tapping range (source notation)Low voltage (kV)Connection group
3156 / 6.3 / 6.6 / 10 / 10.5 / 11±4×2.50.4Dyn11 / Yyn0
4006 / 6.3 / 6.6 / 10 / 10.5 / 11±4×2.50.4Dyn11 / Yyn0
5006 / 6.3 / 6.6 / 10 / 10.5 / 11±4×2.50.4Dyn11 / Yyn0
6306 / 6.3 / 6.6 / 10 / 10.5 / 11±4×2.50.4Dyn11 / Yyn0
8006 / 6.3 / 6.6 / 10 / 10.5 / 11±4×2.50.4Dyn11 / Yyn0
10006 / 6.3 / 6.6 / 10 / 10.5 / 11±4×2.50.4Dyn11 / Yyn0
12506 / 6.3 / 6.6 / 10 / 10.5 / 11±4×2.50.4Dyn11 / Yyn0
16006 / 6.3 / 6.6 / 10 / 10.5 / 11±4×2.50.4Dyn11 / Yyn0
20006 / 6.3 / 6.6 / 10 / 10.5 / 11±4×2.50.4Dyn11 / Yyn0
25006 / 6.3 / 6.6 / 10 / 10.5 / 11±4×2.50.4Dyn11 / Yyn0

Slash-separated entries are alternatives. Tapping notation is retained from the source; where a percent sign or value is absent, request confirmation before selection.

Cooling: natural air (AN); forced-air options should be confirmed for the intended duty. Request voltage combinations, tapping range and connection group for your selected rating.